CVE-2026-58115
Siemens SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) vulnerability
Siemens·SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2)
- Published
- Aug 11, 2026
- Updated
- Nov 4, 2026
- First covered
- Nov 3, 2026
- Latest story
- 2 weeks ago
Summary
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed), SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2) (All versions < V4.3.4-1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.
CWE-306Missing Authentication for Critical Function
Attack profile
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:HAffected products
- Siemens SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2)before V4.3.4-1
- Siemens SIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2)before V4.3.4-1
- Siemens SIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2)before V4.3.4-1
- Siemens SIMATIC IoT2050 SM (6ES7647-0CA00-1AA2)before V4.3.4-1